Informative Annex D is the NEC's set of worked load calculations: D1 and D2 for one-family dwellings, D3 for a store, D4 and D5 for multifamily, D7 for dwelling service conductors and D8 for motors. Exam questions often name an example and ask for one of its numbers. Open your 2020 NEC to Annex D and follow along.
Try this question with your code book open, then check your answer below.
Practice question: Which Informative Annex D example would you use to find the service rating for a one-family dwelling with air conditioning, using the standard method?
- D1(a)
- D3
- D2(c)
- D1(b)
Show the answerHide the answer
The answer: D, Example D1(b)
- D1(b) takes the D1(a) house and adds two room air conditioners, a disposer and a dishwasher. It works out the load on each line and the neutral.
- D1(a) is the same house without air conditioning. D3 is a store. D2(c) uses the optional method for a house with a heat pump.
If the question says "optional method" and air conditioning larger than heating, the answer would be D2(b) instead.
Want hundreds more questions like this one? JCR's $495 self-study package has 500+ practice questions (digital and printed), 100 video lessons, a 152-page study manual and permanent code tabs. Videos and the digital practice exams open right after you order.
Want a live instructor? JCR's live Zoom exam prep class teaches the 2020 NEC in four 4-hour sessions on Tuesday evenings and Saturday mornings, Eastern time, for $800. It fits any exam on the 2020 NEC. Testing in North Carolina? You can also take the two-day in-person class ($845) in Raleigh, Asheville, Mooresville (Charlotte area) or Winston-Salem. 93% pass rate for JCR classroom students.
What Annex D is
- Worked examples, not rules. Annex D is informative. It shows how the Article 220 and 430 rules play out, but it is not a requirement itself.
- Same assumptions every time. The examples use nominal 120, 120/240, 240 and 208Y/120 V, drop fractions of an ampere below 0.5, assume the same power factor for all loads, and use Column C of Table 220.55 for ranges.
- Answers come out in amperes. To pick a wire size, you still go to the Article 310 ampacity tables.
Every Annex D example at a glance
| Example | What it shows | Method |
|---|---|---|
| D1(a) | One-family dwelling, 1,500 ft², 12 kW range, 5.5 kW dryer | Standard (Part III of Article 220) |
| D1(b) | Same house plus air conditioners, disposer and dishwasher | Standard |
| D2(a) | One-family dwelling, heating larger than air conditioning | Optional (220.82) |
| D2(b) | One-family dwelling, air conditioning larger than heating | Optional (220.82) |
| D2(c) | One-family dwelling with a heat pump and 15 kW backup heat | Optional (220.82) |
| D3 | Store building, 4,800 ft² with show window and sign | Standard |
| D3(a) | Industrial feeders in a common raceway | Standard |
| D4(a) and D4(b) | Multifamily dwelling | Standard and optional |
| D5(a) and D5(b) | Multifamily dwelling served at 208Y/120 V, three phase | Standard and optional |
| D6 | Maximum demand for range loads | Table 220.55 |
| D7 | Sizing dwelling service conductors with 310.12 | 310.12 |
| D8 | Motor conductors, overloads, branch-circuit and feeder protection | Article 430 |
| D9 and D10 | Feeder ampacity for elevator generator field control and adjustable speed drives | 430.24 and Article 620 |
| D11 | Mobile home | Article 550 |
Example D1(a), step by step
A 1,500 ft² house with a 12 kW range and a 5.5 kW, 240 V dryer.
| Step | Load |
|---|---|
| General lighting: 1,500 ft² × 3 VA | 4,500 VA |
| Two small-appliance circuits | 3,000 VA |
| Laundry circuit | 1,500 VA |
| Subtotal | 9,000 VA |
| First 3,000 VA at 100% + remaining 6,000 VA at 35% | 3,000 + 2,100 = 5,100 VA |
| Range (Table 220.55) | 8,000 VA |
| Dryer (Table 220.54) | 5,500 VA |
| Net calculated load | 18,600 VA ÷ 240 V = 78 A |
78 A is the calculated load, but 230.42(B) and 230.79 require service conductors and a disconnect rated at least 100 A, so the service is 100 A.
The neutral in D1(a)
This is a common exam question. 220.61 lets you take the range and dryer at 70% on the neutral:
- Lighting and small-appliance load: 5,100 VA
- Range: 8,000 VA × 70% = 5,600 VA
- Dryer: 5,500 VA × 70% = 3,850 VA
- Total: 14,550 VA ÷ 240 V = 61 A
Example D1(b): add the air conditioning
D1(b) starts with D1(a)'s 78 A per line and 61 A on the neutral. Then it adds a 6 A, 230 V room air conditioner, a 12 A, 115 V room air conditioner, an 8 A disposer and a 10 A dishwasher. It also adds 25% of the largest motor, per 430.24.
- Line A: 99 A
- Neutral: 84 A
- Line B: 104 A
The service would be rated 110 A. Notice the two lines carry different loads, because the 115 V loads sit on different lines.
The optional method examples: D2(a), D2(b) and D2(c)
All three use 220.82: the first 10 kVA of general load at 100%, the rest at 40%, then add heating or cooling per 220.82(C). Here's where each lands:
| Example | House | Calculated load | Result |
|---|---|---|---|
| D2(a) | 1,500 ft², 9 kW electric heat, 1.38 kVA air conditioner | 21,480 VA ÷ 240 = 90 A | 100 A minimum service |
| D2(b) | 1,500 ft², six 7 A room air conditioners (10.08 kVA) | 29,200 VA ÷ 240 = 122 A | 122 A service rating |
| D2(c) | 2,000 ft², 24 A heat pump with 15 kW backup heat | 34,790 VA ÷ 240 = 145 A | 150 A service permitted |
The trick in D2(a) and D2(c) is the 220.82(C) comparison. In D2(a), the 1.38 kVA air conditioner is less than 40% of the 9 kVA of heat, so it drops out. In D2(c), the heating selection in 220.82(C)(3) is the heat pump compressor at 100% plus 65% of the backup heat: 5.76 + 9.75 = 15.51 kVA. That is larger than the 5.76 kVA cooling load, so the air conditioning drops out and 15.51 kVA is added.
Three more examples worth knowing
- D3, store building: 80 receptacles at 180 VA (first 10,000 VA at 100%, the rest at 50%), general lighting at 1.9 VA/ft², 200 VA per foot of show window and a 1,200 VA sign circuit. The total comes to 28,520 VA. The connected lighting × 125% was smaller than the Table 220.12 value, so the table value is used.
- D7, dwelling service conductors: 310.12 lets you size them at 83% of the service rating. A 175 A service needs 175 × 0.83 = 145.25 A, so 1/0 copper or 3/0 aluminum at 75°C. In a 100°F ambient with XHHW-2, divide by the 0.91 correction factor: 159.6 A, so 2/0 copper or 4/0 aluminum. See JCR's 310.12 guide.
- D8, motors: three motors on a 480 V feeder. D8 uses nontime-delay fuses: 110 + 40 + 40 = 190 A, so the feeder fuse is 175 A. With an inverse time breaker instead, the same motors give 150 A. JCR walks through it in the motor feeder breaker guide (430.62).
Check yourself
In Example D2(b), the air conditioning is larger than the heating. Is the 1.5 kW bathroom space heater added to the calculation?
Show the answerHide the answer
No. 220.82(C) includes only the largest of its six heating and cooling selections. The 10.08 kVA of air conditioning is larger than the space heater, so D2(b) omits the heater.
Want more practice? Try JCR's free 25-question practice exam.
Common questions
What is the calculated neutral load in Annex D Example D1(a)?
14,550 VA, or 61 A at 240 V. It's 5,100 VA of lighting and small-appliance load plus the range (8,000 VA) and dryer (5,500 VA) each at 70% (220.61).
Which Annex D example covers a one-family dwelling with air conditioning?
D1(b) for the standard method. D2(b) is the optional-method example where air conditioning is larger than heating.
Is Annex D part of the NEC requirements?
No. Annex D is informative. It shows worked examples of the Article 220, 310 and 430 rules but adds no requirements of its own.
What size service does Example D1(a) need?
The calculated load is 78 A, but 230.42(B) and 230.79 set a 100 A minimum, so the service is 100 A.
Which Annex D example covers motor feeders?
Example D8. It covers conductor ampacity, overload protection, branch-circuit protection and feeder protection for three motors on a 480 V feeder.
Written to the 2020 NEC. To follow along, pick up the 2020 NEC or open it online through a paid NFPA LiNK subscription. Our state requirements page shows the edition each state tests.
JCR checked this against the 2020 NEC in NFPA LiNK on October 29, 2026.
Related guides: Dwelling service load calculation, step by step · Service conductor size (310.12) · Electrical exam formulas · How to find NEC answers fast
Get fast at load calculations
Load calculations are some of the most-tested math on electrical exams. JCR's self-study package teaches them step by step, with practice problems that work like the Annex D examples.
Self-study package: $495
- 152-page JCR study manual with a six-week study plan
- 100 video lessons (21 hours) that follow the manual
- Realistic 500+ question mock exam (digital access and on paper)
- Permanent code book tabs
Videos and the digital mock exam arrive by email right after you order. Printed materials ship the same or next business day.
Prefer a classroom? Exam prep workshops: two full days in Raleigh, Asheville, Mooresville (Charlotte area) or Winston-Salem. Or take the live Zoom class: four 4-hour sessions, open to any 2020 NEC exam. Includes all materials (mock exam, videos, study manual) except for NFPA 70 and 72 books. 93% pass rate for JCR classroom students.
Choose your state's self-study package
Each package is built for that state's exam and NEC edition. Pick yours:
Not sure which exam you need? See your state's license and exam requirements.
More worked examples: the 125% continuous load rule, wire size for a 100 A subpanel and all NEC Answers.
Already licensed? CE classes: 8 hours, in person or on Zoom, approved in 20+ states.