A motor feeder's overcurrent device can't be larger than the biggest motor's maximum branch-circuit device rating plus the full-load currents of all the other motors (430.62(A)). If that total isn't a standard size, go down, not up. Open your 2020 NEC to Article 430, Part V and follow along.
Try this question with your code book open, then check your answer below.
Practice question: A feeder supplies two 230 V, 3-phase squirrel-cage motors: one 30 hp and one 25 hp. Each motor branch circuit is protected by a motor short-circuit protector. What is the maximum standard inverse time circuit breaker for the feeder's short-circuit and ground-fault protection?
- 225 A
- 250 A
- 300 A
- 350 A
Show the answerHide the answer
The answer: B, 250 A
- Use Table 430.250 full-load currents, not nameplates (430.6(A)(1)): 30 hp at 230 V is 80 A, and 25 hp is 68 A.
- The motors use motor short-circuit protectors, so 430.62(A) Exception No. 1 applies. Treat each protector as if it were rated at the Table 430.52 maximum for the feeder device type. The feeder device is an inverse time breaker, so that's 250%.
- Largest motor: 80 A × 250% = 200 A. Add the other motor's full-load current: 200 + 68 = 268 A.
- The feeder breaker can't be greater than 268 A, so go down to the standard size below it (240.6(A)): 250 A.
The trap is 300 A, from rounding up. Branch circuits can round up. Feeders can't.
Want hundreds more questions like this one? JCR's $495 self-study package has 500+ practice questions (digital and printed), 100 video lessons, a 152-page study manual and permanent code tabs. Videos and the digital practice exams open right after you order.
Want a live instructor? JCR's live Zoom exam prep class teaches the 2020 NEC in four 4-hour sessions on Tuesday evenings and Saturday mornings, Eastern time, for $800. It fits any exam on the 2020 NEC. Testing in North Carolina? You can also take the two-day in-person class ($845) in Raleigh, Asheville, Mooresville (Charlotte area) or Winston-Salem. 93% pass rate for JCR classroom students.
The rule
For a feeder supplying a specific fixed motor load, 430.62(A) sets the maximum feeder overcurrent device:
- Start with the largest branch-circuit device: the largest rating or setting of the branch-circuit short-circuit and ground-fault protective device for any motor on the feeder, based on the maximum 430.52 allows for that device type.
- Add the other motors: plus the sum of the full-load currents of all the other motors on the feeder.
- Don't round up: the feeder device can't be greater than that total. Pick the standard size at or below it.
- Ties: where two or more branch circuits have the same device rating, count one of them as the largest (430.62(A)).
Step by step
- Get each motor's full-load current from Table 430.250 (3-phase) or Table 430.248 (single-phase), not the nameplate (430.6(A)(1)).
- Size each branch-circuit device with Table 430.52. For squirrel-cage motors other than Design B energy-efficient: 300% for a nontime-delay fuse, 175% for a dual-element fuse, 800% for an instantaneous trip breaker and 250% for an inverse time breaker. If the result isn't a standard size, the branch device may go up to the next standard size (430.52(C)(1) Exception No. 1).
- Find the largest branch device from step 2.
- Add the full-load currents of every other motor on the feeder.
- Pick the feeder device: the standard size from 240.6(A) that doesn't exceed the total.
Standard ratings near the common answers (240.6(A)): 150, 175, 200, 225, 250, 300, 350 and 400 A.
Worked examples
1. Two different motors, inverse time breakers
A 230 V feeder supplies a 30 hp (80 A) and a 25 hp (68 A) squirrel-cage motor, each on an inverse time breaker.
- 30 hp branch breaker: 80 × 250% = 200 A, a standard size.
- Feeder: 200 + 68 = 268 A. Feeder breaker: 250 A.
2. Two identical motors
Two 20 hp, 230 V, 3-phase squirrel-cage motors at 54 A each, each on an inverse time breaker.
- Branch breaker: 54 × 250% = 135 A. Not a standard size, so 150 A is permitted (430.52(C)(1) Exception No. 1).
- Both branch breakers are 150 A, so count one as the largest: 150 + 54 = 204 A.
- Feeder breaker: 200 A.
3. The Annex D example (D8)
Informative Annex D, Example D8 has one 25 hp squirrel-cage motor (34 A at 460 V) and two 30 hp wound-rotor motors (40 A primary). D8 itself uses nontime-delay fuses (last bullet). With an inverse time feeder breaker instead:
- Largest branch device: 25 hp motor, 34 × 250% = 85 A, which goes up to 90 A.
- Feeder: 90 + 40 + 40 = 170 A. Feeder breaker: 150 A.
- D8's own answer, with nontime-delay fuses: 34 × 300% = 102 A, up to 110 A. Then 110 + 40 + 40 = 190 A, so a 175 A fuse.
See every Annex D example in JCR's Annex D guide.
Three rules that change the answer
- Instantaneous trip breakers and motor short-circuit protectors: they're allowed at very high settings. For the feeder math, assume each one is rated at the Table 430.52 maximum for the type of feeder device you're using (430.62(A) Exception No. 1). That's the step that solves the practice question.
- Bigger feeder conductors: where the feeder conductors have more ampacity than 430.24 requires, the feeder device may be based on the conductors' ampacity instead (430.62(B)).
- Motors plus other loads: the feeder device must be rated at least the sum of the other loads plus the 430.62 value for the motors (430.63).
Don't forget the feeder conductors
The conductors are sized separately by 430.24: 125% of the largest motor's full-load current, plus the full-load currents of the other motors, plus 100% of noncontinuous and 125% of continuous non-motor loads.
For example 1: 80 × 125% + 68 = 168 A of conductor ampacity. For example 2: 54 × 125% + 54 = 121.5 A.
Check yourself
A 460 V feeder supplies three 3-phase squirrel-cage motors: 50 hp (65 A), 25 hp (34 A) and 10 hp (14 A). Each motor branch circuit has dual-element (time-delay) fuses, and the feeder uses dual-element fuses too. What is the maximum feeder fuse?
Show the answerHide the answer
- Largest branch fuse: 65 × 175% = 113.75 A. The next standard size up is 125 A (430.52(C)(1) Exception No. 1).
- Feeder: 125 + 34 + 14 = 173 A.
- The standard size that doesn't exceed 173 A is 150 A.
Want more practice? Try JCR's free 25-question practice exam.
Common questions
How do you size a feeder breaker for several motors?
Take the largest motor's maximum branch-circuit device rating from 430.52, add the full-load currents of the other motors, and pick the standard size that doesn't exceed the total (430.62(A)).
Can you round up the feeder overcurrent device for motors?
No. 430.62(A) says the feeder device can't be greater than the calculated value, so you go down to a standard size. Only the branch-circuit device may round up to the next standard size (430.52(C)(1) Exception No. 1).
What if the motors use motor short-circuit protectors or instantaneous trip breakers?
For the feeder calculation, assume each one is rated at the Table 430.52 maximum percentage for the type of feeder device used (430.62(A) Exception No. 1).
Do you use nameplate or table full-load current for motor feeders?
Use Tables 430.247 through 430.250, not the nameplate, for general motor applications (430.6(A)(1)). Low-speed, high-torque and multispeed motors use the nameplate.
What size feeder conductors do two motors need?
125% of the largest motor's full-load current plus the full-load currents of the other motors (430.24). For a 30 hp (80 A) and a 25 hp (68 A) motor at 230 V, that's 168 A.
Written to the 2020 NEC. To follow along, pick up the 2020 NEC or open it online through a paid NFPA LiNK subscription. Our state requirements page shows the edition each state tests.
JCR checked this against the 2020 NEC in NFPA LiNK on October 29, 2026.
Related guides: Motor branch-circuit breaker size (Table 430.52) · Motor overload sizing (430.32) · The 125% continuous load rule · NEC Annex D examples explained
Master motor calculations
Motor branch circuits, overloads and feeders show up on almost every electrical exam. JCR's self-study package drills them step by step, with practice problems like the ones above.
Self-study package: $495
- 152-page JCR study manual with a six-week study plan
- 100 video lessons (21 hours) that follow the manual
- Realistic 500+ question mock exam (digital access and on paper)
- Permanent code book tabs
Videos and the digital mock exam arrive by email right after you order. Printed materials ship the same or next business day.
Prefer a classroom? Exam prep workshops: two full days in Raleigh, Asheville, Mooresville (Charlotte area) or Winston-Salem. Or take the live Zoom class: four 4-hour sessions, open to any 2020 NEC exam. Includes all materials (mock exam, videos, study manual) except for NFPA 70 and 72 books. 93% pass rate for JCR classroom students.
Choose your state's self-study package
Each package is built for that state's exam and NEC edition. Pick yours:
Not sure which exam you need? See your state's license and exam requirements.
More worked examples: ampacity adjustment and temperature correction, voltage drop and all NEC Answers.
Already licensed? CE classes: 8 hours, in person or on Zoom, approved in 20+ states.