This question is from JCR's 500+ question mock exam. 87% of students got this wrong. Try it with your code book open, then check your answer below.
Show the answerHide the answer
The answer: D, 150 amperes
- 54 A × 250% = 135 A.
- 135 A is not a standard size, so go to the next standard size: 150 A.
The most common wrong answer was 135 A: the right math, but no round-up to a standard size. The autotransformer starting is a distraction. The 2020 Table 430.52 has no starting-method column, so the inverse time breaker is still 250%.
The question gives the current (54 A) but no horsepower or voltage, so use 54 A. On the job, look up the table FLC by horsepower and voltage (Step 1 below).
This breaker protects against short circuits and ground faults only. Size the branch-circuit conductors at 125% of FLC (430.22), and size overload protection from the nameplate current (430.32).
Want hundreds more questions like this one? JCR's $495 self-study package has 500+ practice questions (digital and printed), 100 video lessons, a 152-page study manual and permanent code tabs. Videos and the digital practice exams open right after you order.
Testing in North Carolina? Take JCR's NC exam prep class: two full days in person ($845) in Raleigh, Asheville, Mooresville (Charlotte area) or Winston-Salem, or live on Zoom on Tuesday evenings and Saturday mornings. 93% pass rate for JCR classroom students.
The rule
For a three-phase squirrel-cage motor, the inverse time breaker that protects the branch circuit from short circuits and ground faults can be up to 250% of the motor's full-load current (FLC) from the motor tables in the 2020 NEC (NFPA 70). If 250% is not a standard size, 430.52(C)(1) Exception No. 1 lets you go up to the next standard size in 240.6(A).
Motor breaker size calculator (Table 430.52)
Pick the motor type and protective device, then look up the full-load current by horsepower and voltage or type it in. The calculator applies the Table 430.52 percentage, rounds up to the next standard size and shows the start-up limit.
Table FLC per 430.6(A)(1). Motors under 1200 RPM, high-torque motors and multispeed motors use the nameplate current. Standard sizes from 240.6(A). Motor circuits of 1000 V or less. Instantaneous-trip breakers aren't covered.
Step 1: Get FLC from the table, not the nameplate
For branch-circuit short-circuit and ground-fault protection, 430.6(A)(1) sends you to the motor tables instead of the nameplate: Table 430.248 for single-phase motors and Table 430.250 for three-phase motors. Look up the motor by horsepower and voltage.
The nameplate current is for separate overload protection, not this step (430.6(A)(2)). One catch: motors built for low speeds (less than 1200 RPM) or high torques, and multispeed motors, use the nameplate current (430.6(A)(1)).
Step 2: Multiply by the Table 430.52 percentage
Find your motor type in Table 430.52, then read the inverse time breaker column:
- Single-phase motors: 250%
- AC polyphase motors other than wound-rotor (squirrel cage, including Design B energy-efficient): 250%
- Synchronous: 250%. Low-torque, low-speed synchronous motors (usually 450 rpm or lower) that start unloaded don't need more than 200% (footnote 3).
- Wound-rotor: 150%
- DC (constant voltage): 150%
The same table has columns for nontime-delay fuses, dual-element (time-delay) fuses and instantaneous trip breakers. Use the column for the device you are installing. Whatever device you pick must be able to carry the motor's starting current (430.52(B)).
Step 3: Round up to the next standard size if needed
If your result is not a standard rating, 430.52(C)(1) Exception No. 1 lets you use the next higher standard size from 240.6(A). Standard sizes in this range: 60, 70, 80, 90, 100, 110, 125, 150, 175 and 200 A.
Worked example
A 25 hp, 460 V, three-phase squirrel-cage motor:
- Table 430.250: FLC = 34 A.
- 34 A × 250% = 85 A.
- 85 A is not a standard size. The next standard size up is 90 A.
Answer: 90 A maximum inverse time breaker.
If the motor won't start
If the breaker from Step 3 can't handle the starting current, 430.52(C)(1) Exception No. 2(3) lets you go larger. An inverse time breaker can't exceed 400% of FLC for motors with FLC of 100 A or less, or 300% for FLC over 100 A. There is no rounding up past this limit.
In the example: 34 A × 400% = 136 A. The largest standard breaker that does not exceed 136 A is 125 A.
One more limit: if the manufacturer's overload relay table, or a marking on the equipment, shows a lower maximum, don't exceed it (430.52(C)(2)).
Same motor, with dual-element fuses
Table 430.52 gives dual-element (time-delay) fuses 175% instead of 250%. For the same 25 hp, 460 V motor: 34 A × 175% = 59.5 A. The next standard size up in 240.6(A) is 60 A.
If the motor won't start on those, Exception No. 2(2) lets time-delay fuses go up to 225% of FLC: 34 A × 225% = 76.5 A, so 70 A is the largest standard size that doesn't exceed it.
Same motor, different device, different answer. Always read the column for what you're installing.
Want more practice? Try JCR's free 25-question practice exam.
Common questions
What size breaker for a 25 hp, 460 V three-phase motor?
Up to a 90 A inverse time breaker for a squirrel-cage motor. Table 430.250 gives 34 A, × 250% = 85 A, and the next standard size is 90 A.
Do you round up when sizing a motor breaker?
Yes, once. If the Table 430.52 result isn't a standard size, you may go to the next higher standard rating (430.52(C)(1) Exception No. 1). Past that, only the starting-current limits in Exception No. 2 allow more.
Is the motor breaker sized from the nameplate?
For most motors, no. Use the full-load current from Table 430.248 or 430.250 (430.6(A)(1)). The nameplate is for overload sizing.
Is there a motor breaker sizing chart?
Table 430.52 is the chart. It sets a maximum percentage of the table full-load current for each motor type and protective device, such as 250% for an inverse time breaker on a squirrel-cage motor. The calculator above does the math and the round-up.
This answer uses the 2020 NEC. You can buy the 2020 NEC here or view it online with a paid NFPA LiNK subscription. Check which NEC edition your state tests on.
JCR checked this answer against the 2020 NEC in NFPA LiNK on October 21, 2026.
Related guides: Motor overload sizing and service factor (430.32) · The 5 most-missed questions on JCR's free practice exam · Ampacity derating step by step
More free lessons on the JCR YouTube channel
Practice motor math before test day
Breakers, conductors and overloads each use a different rule. JCR's self-study package drills all three until you stop mixing them up.
Self-study package: $495
- 152-page JCR study manual with a six-week study plan
- 100 video lessons (21 hours) that follow the manual
- Realistic 500+ question mock exam (digital access and on paper)
- Permanent code book tabs
Videos and the digital mock exam arrive by email right after you order. Printed materials ship the same business day.
Prefer a classroom? Exam prep workshops: two full days in Raleigh, Asheville, Mooresville (Charlotte area), Winston-Salem, or live on Zoom. Includes all materials (mock exam, videos, study manual) except for NFPA 70 and 72 books. 93% pass rate for JCR classroom students.
Choose your state's self-study package
Each package is built for that state's exam and NEC edition. Pick yours:
Not sure which exam you need? See your state's license and exam requirements.
More worked examples: all NEC Answers.
Already licensed? CE classes: 8 hours, in person or on Zoom, approved in 20+ states.