How to Size a Motor Breaker: NEC Table 430.52 (2020 NEC)

Sizing a motor breaker with NEC Table 430.52 - JCR Productions

Exam question: maximum inverse time breaker for a squirrel cage motor with a 54-ampere FLA

This question is from JCR's 500+ question mock exam. 87% of students got this wrong. Try it with your code book open, then check your answer below.

Show the answerHide the answer

The answer: D, 150 amperes

  • 54 A × 250% = 135 A.
  • 135 A is not a standard size, so go to the next standard size: 150 A.

The most common wrong answer was 135 A: the right math, but no round-up to a standard size. The autotransformer starting is a distraction. The 2020 Table 430.52 has no starting-method column, so the inverse time breaker is still 250%.

The question gives the current (54 A) but no horsepower or voltage, so use 54 A. On the job, look up the table FLC by horsepower and voltage (Step 1 below).

This breaker protects against short circuits and ground faults only. Size the branch-circuit conductors at 125% of FLC (430.22), and size overload protection from the nameplate current (430.32).

Want hundreds more questions like this one? JCR's $495 self-study package has 500+ practice questions (digital and printed), 100 video lessons, a 152-page study manual and permanent code tabs. Videos and the digital practice exams open right after you order.

Pick your state's package

Testing in North Carolina? Take JCR's NC exam prep class: two full days in person ($845) in Raleigh, Asheville, Mooresville (Charlotte area) or Winston-Salem, or live on Zoom on Tuesday evenings and Saturday mornings. 93% pass rate for JCR classroom students.

See NC class dates

The rule

For a three-phase squirrel-cage motor, the inverse time breaker that protects the branch circuit from short circuits and ground faults can be up to 250% of the motor's full-load current (FLC) from the motor tables in the 2020 NEC (NFPA 70). If 250% is not a standard size, 430.52(C)(1) Exception No. 1 lets you go up to the next standard size in 240.6(A).

Motor breaker size calculator (Table 430.52)

Pick the motor type and protective device, then look up the full-load current by horsepower and voltage or type it in. The calculator applies the Table 430.52 percentage, rounds up to the next standard size and shows the start-up limit.

Pick the motor and device.

Table FLC per 430.6(A)(1). Motors under 1200 RPM, high-torque motors and multispeed motors use the nameplate current. Standard sizes from 240.6(A). Motor circuits of 1000 V or less. Instantaneous-trip breakers aren't covered.

Step 1: Get FLC from the table, not the nameplate

For branch-circuit short-circuit and ground-fault protection, 430.6(A)(1) sends you to the motor tables instead of the nameplate: Table 430.248 for single-phase motors and Table 430.250 for three-phase motors. Look up the motor by horsepower and voltage.

The nameplate current is for separate overload protection, not this step (430.6(A)(2)). One catch: motors built for low speeds (less than 1200 RPM) or high torques, and multispeed motors, use the nameplate current (430.6(A)(1)).

Step 2: Multiply by the Table 430.52 percentage

Find your motor type in Table 430.52, then read the inverse time breaker column:

  • Single-phase motors: 250%
  • AC polyphase motors other than wound-rotor (squirrel cage, including Design B energy-efficient): 250%
  • Synchronous: 250%. Low-torque, low-speed synchronous motors (usually 450 rpm or lower) that start unloaded don't need more than 200% (footnote 3).
  • Wound-rotor: 150%
  • DC (constant voltage): 150%

The same table has columns for nontime-delay fuses, dual-element (time-delay) fuses and instantaneous trip breakers. Use the column for the device you are installing. Whatever device you pick must be able to carry the motor's starting current (430.52(B)).

Step 3: Round up to the next standard size if needed

If your result is not a standard rating, 430.52(C)(1) Exception No. 1 lets you use the next higher standard size from 240.6(A). Standard sizes in this range: 60, 70, 80, 90, 100, 110, 125, 150, 175 and 200 A.

Worked example

A 25 hp, 460 V, three-phase squirrel-cage motor:

  1. Table 430.250: FLC = 34 A.
  2. 34 A × 250% = 85 A.
  3. 85 A is not a standard size. The next standard size up is 90 A.

Answer: 90 A maximum inverse time breaker.

If the motor won't start

If the breaker from Step 3 can't handle the starting current, 430.52(C)(1) Exception No. 2(3) lets you go larger. An inverse time breaker can't exceed 400% of FLC for motors with FLC of 100 A or less, or 300% for FLC over 100 A. There is no rounding up past this limit.

In the example: 34 A × 400% = 136 A. The largest standard breaker that does not exceed 136 A is 125 A.

One more limit: if the manufacturer's overload relay table, or a marking on the equipment, shows a lower maximum, don't exceed it (430.52(C)(2)).

Same motor, with dual-element fuses

Table 430.52 gives dual-element (time-delay) fuses 175% instead of 250%. For the same 25 hp, 460 V motor: 34 A × 175% = 59.5 A. The next standard size up in 240.6(A) is 60 A.

If the motor won't start on those, Exception No. 2(2) lets time-delay fuses go up to 225% of FLC: 34 A × 225% = 76.5 A, so 70 A is the largest standard size that doesn't exceed it.

Same motor, different device, different answer. Always read the column for what you're installing.

Want more practice? Try JCR's free 25-question practice exam.

Common questions

What size breaker for a 25 hp, 460 V three-phase motor?

Up to a 90 A inverse time breaker for a squirrel-cage motor. Table 430.250 gives 34 A, × 250% = 85 A, and the next standard size is 90 A.

Do you round up when sizing a motor breaker?

Yes, once. If the Table 430.52 result isn't a standard size, you may go to the next higher standard rating (430.52(C)(1) Exception No. 1). Past that, only the starting-current limits in Exception No. 2 allow more.

Is the motor breaker sized from the nameplate?

For most motors, no. Use the full-load current from Table 430.248 or 430.250 (430.6(A)(1)). The nameplate is for overload sizing.

Is there a motor breaker sizing chart?

Table 430.52 is the chart. It sets a maximum percentage of the table full-load current for each motor type and protective device, such as 250% for an inverse time breaker on a squirrel-cage motor. The calculator above does the math and the round-up.

This answer uses the 2020 NEC. You can buy the 2020 NEC here or view it online with a paid NFPA LiNK subscription. Check which NEC edition your state tests on.

JCR checked this answer against the 2020 NEC in NFPA LiNK on October 21, 2026.

Related guides: Motor overload sizing and service factor (430.32) · The 5 most-missed questions on JCR's free practice exam · Ampacity derating step by step

More free lessons on the JCR YouTube channel

Practice motor math before test day

Breakers, conductors and overloads each use a different rule. JCR's self-study package drills all three until you stop mixing them up.

JCR 2020 NEC self-study package with study manual and mock exam booklet

Self-study package: $495

  • 152-page JCR study manual with a six-week study plan
  • 100 video lessons (21 hours) that follow the manual
  • Realistic 500+ question mock exam (digital access and on paper)
  • Permanent code book tabs

Videos and the digital mock exam arrive by email right after you order. Printed materials ship the same business day.

Pick your state's package

Prefer a classroom? Exam prep workshops: two full days in Raleigh, Asheville, Mooresville (Charlotte area), Winston-Salem, or live on Zoom. Includes all materials (mock exam, videos, study manual) except for NFPA 70 and 72 books. 93% pass rate for JCR classroom students.

Choose your state's self-study package

Each package is built for that state's exam and NEC edition. Pick yours:

Not sure which exam you need? See your state's license and exam requirements.

More worked examples: all NEC Answers.

Already licensed? CE classes: 8 hours, in person or on Zoom, approved in 20+ states.