The equipment grounding conductor is sized by the breaker or fuse protecting the circuit, not by the size of the hot wires. Under Table 250.122 of the 2020 NEC (NFPA 70), a 20 A circuit needs at least 12 AWG copper. A 100 A circuit needs 8 AWG copper, and 200 A needs 6 AWG copper. Upsized hots and parallel runs change the answer, as shown below.
| Quick facts | Equipment grounding conductor (2020 NEC) |
|---|---|
| What it is | The equipment grounding conductor (EGC) is the ground wire from metal boxes and equipment back to the source. If a hot faults to a box, it carries enough current to trip the breaker. |
| What sets the size | The rating of the overcurrent device (breaker or fuse) ahead of the circuit. Use the Table 250.122 row equal to or just above that rating. |
| Size limit | The EGC never has to be bigger than the circuit conductors (250.122(A)). |
| Hots made bigger | Increase the EGC by the same circular-mil ratio (250.122(B)). Exception: hots upsized only for temperature correction or bundling under 310.15(B) or (C). |
| Parallel runs | Each raceway or cable gets its own EGC, sized from the full overcurrent device rating (250.122(F)). |
| Motor circuits | Size from the motor's short-circuit and ground-fault breaker or fuse rating (250.122(D)). |
Table 250.122 equipment grounding conductor calculator
Enter the breaker or fuse rating. Table 250.122 rows mean "not exceeding," so a rating between rows uses the larger row: a 30 A, 40 A or 50 A circuit uses the 60 A row, 10 AWG copper. If you made the hots bigger, the calculator applies the 250.122(B) increase too.
Wire-type ground in the same metal as the hots. Areas come from Chapter 9, Table 8. Doesn't cover the qualified-person exception to 250.122(B).
The table runs to 6000 A. "Aluminum" includes copper-clad aluminum. "kcmil" means thousands of circular mils, the unit for wire cross-section.
Studying for your electrical exam? JCR's $495 self-study package has 500+ practice questions (digital and printed), 100 video lessons, a 152-page study manual and permanent code tabs. Videos and the digital practice exams open right after you order.
Testing in North Carolina? Take JCR's NC exam prep class: two full days in person ($845) in Raleigh, Asheville, Mooresville (Charlotte area) or Winston-Salem, or live on Zoom on Tuesday evenings and Saturday mornings. 93% pass rate for JCR classroom students.
How to find equipment grounding conductor size
- Find the breaker or fuse rating. Ignore the load and the wire ampacity.
- Go down Table 250.122 to the first row equal to or larger than that rating.
- If the hots were upsized for a reason other than 310.15(B) or (C), upsize the EGC (Example 1).
- For parallel sets, put a full-size EGC in every raceway or cable (Example 2).
Example 1: hots upsized for voltage drop (250.122(B))
A 200 A feeder would normally use 3/0 copper (200 A at 75°C, Table 310.16). For voltage drop, the designer pulls 250 kcmil copper. Areas come from Chapter 9, Table 8.
- Table 250.122 at 200 A: 6 AWG copper, 26,240 circular mils.
- Ratio: 250,000 ÷ 167,800 (3/0) = 1.49.
- New area: 26,240 × 1.49 = about 39,094 circular mils.
- 6 AWG is too small. The next size, 4 AWG, has 41,740 circular mils.
- Answer: 4 AWG copper EGC.
Example 2: a 400 A parallel feeder (250.122(F))
A 400 A breaker feeds two sets of 3/0 copper (200 A each at 75°C), one set per PVC conduit. Parallel conductors must be 1/0 or larger (310.10(G)), so 3/0 qualifies.
- Table 250.122 at 400 A: 3 AWG copper.
- PVC can't be the ground path, so each conduit needs a wire-type EGC.
- Pull a 3 AWG copper EGC in each conduit and connect them in parallel.
Tabbing Article 250? Use the 2020 NEC softbound book so your tabs match the edition this guide covers.
Common Table 250.122 exam traps
- Sizing from the wire. A 100 A breaker gets 8 AWG copper no matter what size the hots are.
- Using the 2017 trigger. In 2017, any upsizing triggered the increase. The 2020 text exempts upsizing required by 310.15(B) or (C), like hot-ambient correction or bundling.
- Rounding down. If the math lands between sizes, take the larger one.
- Halving the EGC on parallel runs. Each raceway or cable gets a full-size EGC.
- Motor circuits. Size from the motor's branch-circuit breaker or fuse, then apply the limit. 14 AWG motor conductors on a 40 A breaker need only a 14 AWG EGC. JCR's Table 430.52 guide shows how that breaker is chosen.
Some states test or enforce an older edition, such as the 2017 NEC on Tennessee's exam. Find your state's edition in NEC adoption by state or on JCR's state requirements page.
Equipment grounding conductor questions
What size ground wire do I need?
It depends on the breaker or fuse, not the hot wires. Table 250.122 calls for at least 14 AWG copper up to 15 A, 12 AWG up to 20 A, 10 AWG up to 60 A, 8 AWG up to 100 A and 6 AWG up to 200 A.
What size ground wire do I need for a 200 amp feeder?
6 AWG copper or 4 AWG aluminum, from Table 250.122. Service equipment uses different bonding rules, covered in JCR's main bonding jumper guide.
What size ground wire for a 100 amp subpanel?
At least 8 AWG copper or 6 AWG aluminum. That comes straight from the 100 A row of Table 250.122.
Do I have to upsize the ground wire when I upsize for voltage drop?
Yes. Section 250.122(B) says a wire-type EGC grows in proportion to the hots' circular-mil increase. Exceptions: upsizing for 310.15(B) or (C), or an EGC sized by a qualified person for an effective ground-fault path.
Does each conduit in a parallel run need its own ground wire?
Yes. Each raceway gets a wire-type EGC sized from the full overcurrent device rating. Metal raceways that qualify under 250.118 can serve as the EGC instead.
Can one ground wire serve several circuits in the same conduit?
Yes. Section 250.122(C) allows one EGC for several circuits in a raceway, cable, trench or cable tray. Size it for the largest breaker or fuse among them.
Learn the grounding tables the way the exam asks them
JCR's $495 self-study package covers Article 250 with video lessons, digital practice exams and the JCR workbook. Videos and practice exams open at checkout. The workbook ships the same business day.
Prefer a classroom? JCR runs two-day exam prep workshops in Raleigh, Asheville, Mooresville (Charlotte area) and Winston-Salem, or live on Zoom.
Get the self-study package — $495
Want a quick check first? Try 25 free NEC practice questions.
Choose your state's self-study package
Each package is built for that state's exam and NEC edition. Pick yours:
Not sure which exam you need? See your state's license and exam requirements.
Related guides: Main bonding jumper size (250.28) · Voltage drop calculation · 200 amp service wire size (Table 310.12)
More worked examples: grounding electrode conductor size (Table 250.66) and all NEC Answers.
References
- NFPA 70, National Electrical Code, 2020 edition
- 2020 NEC 250.122(A), (B), (C), (D) and (F)
- 2020 NEC Table 250.122
- 2020 NEC 310.10(G)(1), parallel conductors
- 2020 NEC Table 310.16, ampacities
- 2020 NEC Chapter 9, Table 8, conductor properties
JCR checked every section and table value above against the 2020 NEC in NFPA LiNK on October 21, 2026.