100%-Rated Breakers and Continuous Loads (NEC 210.20(A))

100%-rated breakers and continuous loads, NEC 210.20(A) - JCR Productions

Exam question: maximum continuous load when the assembly is listed for 100 percent operation

Most-missed NEC mock exam question #2 of 5, from JCR's free 25-question NEC mock exam. 71% of students got this wrong. Try it with your 2020 NEC open, then check your answer below.

Show the answerHide the answer

The answer: C, 100 percent

Normally, a branch-circuit overcurrent device must be rated at least the noncontinuous load plus 125% of the continuous load. The exception to 210.20(A) drops the 125% when the assembly, including the overcurrent devices, is listed for operation at 100% of its rating.

This question says the complete assembly is listed for 100%. So the exception applies.

The trap: 80 percent

80 percent was the top wrong answer, picked by 41% of students. It comes from the normal rule: a breaker sized at 125% of a continuous load carries that load at 1 ÷ 1.25 = 80% of its rating.

That math is right for a standard assembly. It doesn't fit here, because the question gives you an assembly listed for 100%.

Want hundreds more questions like this one? JCR's $495 self-study package has 500+ practice questions (digital and printed), 100 video lessons, a 152-page study manual and permanent code tabs. Videos and the digital practice exams open right after you order.

Pick your state's package

Testing in North Carolina? Take JCR's NC exam prep class: two full days in person ($845) in Raleigh, Asheville, Mooresville (Charlotte area) or Winston-Salem, or live on Zoom on Tuesday evenings and Saturday mornings. 93% pass rate for JCR classroom students.

See NC class dates

What 210.20(A) says

  • Continuous load: a load where the maximum current is expected to continue for 3 hours or more (Article 100).
  • Normal rule: overcurrent device rating not less than the noncontinuous load plus 125% of the continuous load.
  • Exception: where the assembly, including the overcurrent devices protecting the branch circuit(s), is listed for operation at 100% of its rating, the rating may be not less than the continuous load plus the noncontinuous load. A 100%-rated breaker alone isn't enough. The listing has to cover the assembly.
  • Conductors: still protected in accordance with 240.4 (210.20(B)).

Worked example

A branch circuit supplies 32 A of continuous load and 8 A of noncontinuous load.

  • Standard assembly: 8 + (32 × 125%) = 8 + 40 = 48 A minimum. The next standard size in 240.6(A) is 50 A.
  • Assembly listed for 100%: 32 + 8 = 40 A minimum.

Common questions

Do I need a 100% rated breaker for continuous loads?

No. A standard breaker works if you size it at the noncontinuous load plus 125% of the continuous load. The 100% option only lets you skip the extra 25%, and only when the whole assembly is listed for it.

What is a continuous load?

Article 100 defines it as a load where the maximum current is expected to continue for 3 hours or more. Lighting in stores and offices that stays on all day is a common example.

Is a 100% rated breaker enough by itself?

No. The exception in 210.20(A) requires the assembly, including its overcurrent devices, to be listed for 100% operation. Check the equipment's listing and marking before you drop the 125%.

All references are to the 2020 NEC. Order the code book here, or read it online through a paid NFPA LiNK subscription. Our state requirements page lists the edition each state tests.

JCR checked this against the 2020 NEC in NFPA LiNK on October 21, 2026.

Related guides: Dwelling service load calculation, step by step · 200 amp service wire size (Table 310.12) · The 5 most-missed NEC mock exam questions

The 5 most-missed NEC mock exam questions

  1. Pull box size for an angle pull (314.28)
  2. Continuous loads on a 100%-rated assembly (210.20(A)) (this post)
  3. Breakers used as switches: SWD and HID (240.83(D))
  4. Motor overload sizing and service factor (430.32)
  5. Closet light clearance (410.16(C))

See all 5 most-missed questions on one page.

Free video: the 125% rule

The conductor side of this rule works the same way. Watch JCR's lesson on the 125% rule for conductors (210.19), or see all JCR lessons on YouTube.

Turn tricky exceptions into easy points

Exam questions love exceptions like this one. JCR's self-study package teaches you where to find them, fast.

JCR 2020 NEC self-study package with study manual and mock exam booklet

Self-study package: $495

  • 152-page JCR study manual with a six-week study plan
  • 100 video lessons (21 hours) that follow the manual
  • Realistic 500+ question mock exam (digital access and on paper)
  • Permanent code book tabs

Videos and the digital mock exam arrive by email right after you order. Printed materials ship the same business day.

Pick your state's package

Prefer a classroom? Exam prep workshops: two full days in Raleigh, Asheville, Mooresville (Charlotte area), Winston-Salem, or live on Zoom. Includes all materials (mock exam, videos, study manual) except for NFPA 70 and 72 books. 93% pass rate for JCR classroom students.

Choose your state's self-study package

Each package is built for that state's exam and NEC edition. Pick yours:

Not sure which exam you need? See your state's license and exam requirements.

More worked examples: all NEC Answers.

Already licensed? CE classes: 8 hours, in person or on Zoom, approved in 20+ states.