2017 NEC pool wiring requirements, all measured from the inside wall of the pool. No receptacle closer than 6 ft. One required receptacle between 6 ft and 20 ft at a permanently installed pool. GFCI on 125 V, 15 A and 20 A receptacles within 20 ft. Outdoor lights and fans within 5 ft at least 12 ft above the maximum water level. Use 8 AWG solid copper for equipotential bonding. Pool pump motor GFCI in 2017 680.21(C) covers outlets on single-phase, 120 V through 240 V branch circuits with no ampere limit, but not 3-phase pumps, which the 2020 rule added.
Pool distances show up on the exams in all five 2017 NEC states, and several numbers moved in later editions. Taking the 2020 NEC instead? Use JCR's 2020 NEC GFCI requirements guide. Want a quick score check? The free 2017 NEC mock has 25 questions with instant feedback.
Article 680 questions are mostly distances and sizes. Easy points, if you study the 2017 values your Tennessee, Nevada, Arizona, Kansas or Missouri exam grades.
The $495 course includes 100 video lessons totaling 21 hours, the 152-page printed 2017 NEC manual, 312 online practice questions with a pausable 100-question timed mock, a printed mock booklet and permanent tabs.
2017 NEC pool wiring requirements at a glance
| Rule | 2017 NEC requirement |
|---|---|
| Required receptacle, 680.22(A)(1) | At any permanently installed pool: at least one 125 V, 15 A or 20 A receptacle on a general-purpose branch circuit, 6 ft to 20 ft from the inside wall and no more than 6 ft 6 in. above the floor, platform or grade serving the pool |
| Pump and sanitation receptacles, 680.22(A)(2) | At least 6 ft from the inside wall, GFCI protected, grounding type |
| Other receptacles, 680.22(A)(3) | At least 6 ft from the inside wall |
| Receptacle GFCI, 680.22(A)(4) | Every 125 V, 15 A or 20 A receptacle within 20 ft of the inside wall |
| Outdoor lights and paddle fans, 680.22(B)(1) | Over the pool or within 5 ft horizontally: at least 12 ft above the maximum water level |
| Switches, 680.22(C) | At least 5 ft horizontally, unless behind a solid fence, wall or other permanent barrier, or listed for use within 5 ft |
| Pump motor GFCI, 680.21(C) | Outlets on single-phase, 120 V through 240 V branch circuits, any ampere rating, plug-in or hard-wired |
| Bonding, 680.26(B) | Solid copper, insulated, covered or bare, 8 AWG minimum. Perimeter surface 3 ft out from the inside walls |
Bonding and grounding do different jobs at a pool. If that difference is fuzzy, JCR's grounding vs bonding explainer clears it up, and 2020 NEC changes vs. 2017 lists the bigger edition shifts.
Pool receptacle distance: the 6 ft and 20 ft rings
- Inside 6 ft: no receptacles, the pump receptacle included.
- 6 ft to 20 ft: where the required receptacle goes, no higher than 6 ft 6 in. above the deck or grade, and where 125 V, 15 A and 20 A receptacles need GFCI.
- Measure from the water side. Every 680.22 distance starts at the inside wall of the pool, not the deck edge or the fence.
Pool pump GFCI: 2017 vs 2020 (680.21(C))
| Edition | Which pool motor outlets need GFCI |
|---|---|
| 2017 NEC | Pool pump motors on single-phase, 120 V through 240 V branch circuits, whether by receptacle or direct connection. No ampere limit. 3-phase pumps are not covered. |
| 2020 NEC | All pool motors on branch circuits rated 150 V or less to ground and 60 A or less, single- or 3-phase |
So a 208 V, 20 A, 3-phase pump needs no GFCI under 2017 680.21(C) but does under the 2020 rule, while a 240 V, 30 A single-phase pump needs GFCI under both. On a 2017 exam, answer with the 2017 scope.
Pool motor wiring methods, 680.21(A)
In 2017 the motor wiring method depends on the corrosive environment in 680.14(A), which includes areas with circulation pumps, filters, chlorinators or stored pool chemicals.
- Corrosive area: a method identified for it, such as RMC, IMC, rigid PVC or RTRC (680.14(B)), or MC cable listed for the location, with an insulated copper EGC from Table 250.122, 12 AWG minimum (680.21(A)(1)).
- Noncorrosive area: the general Chapter 3 rules.
- Flexible connections: liquidtight flexible metal or nonmetallic conduit with listed fittings (680.21(A)(2)).
- Cord-and-plug: a cord 3 ft or shorter with a copper EGC of at least 12 AWG and a grounding-type plug (680.21(A)(3)).
Pool lights, ceiling fans and switches (680.22(B) and (C))
- Outdoors, new work: luminaires, lighting outlets and paddle fans over the pool or within 5 ft of the inside wall go at least 12 ft above the maximum water level.
- Indoors: same 12 ft unless the branch circuit is GFCI protected. Then totally enclosed luminaires and paddle fans identified for use beneath ceiling structures may be as low as 7 ft 6 in.
- Existing luminaires within 5 ft: at least 5 ft above the maximum water level, rigidly attached and GFCI protected.
- 5 ft to 10 ft out: GFCI unless at least 5 ft above the maximum water level and rigidly attached to the structure.
- Switches: 5 ft horizontally, unless a permanent barrier separates them or the switch is listed for use closer.
Pool bonding requirements: equipotential bonding in 680.26
The goal is to hold every conductive part around the pool at the same potential so a swimmer never bridges a voltage difference. Under 680.26(B), the 8 AWG or larger solid copper bonding conductor does not have to be extended to a panelboard, service equipment or electrode.
- Conductor: solid copper, insulated, covered or bare, at least 8 AWG, or rigid metal conduit of brass or another identified corrosion-resistant metal.
- Perimeter surface: 3 ft out from the inside walls, paved or unpaved. If a permanent wall or building at least 5 ft tall is closer than 3 ft, bond only the pool side.
- Tie-in: attach the perimeter bonding to the pool's reinforcing steel or copper grid at a minimum of four points, uniformly spaced (not required for nonconductive pool shells).
- Copper ring: where reinforcing steel isn't available or is encapsulated in a nonconductive compound, at least one 8 AWG bare solid copper conductor follows the perimeter 18 in. to 24 in. from the inside walls, 4 in. to 6 in. below the subgrade, with listed splices only.
- Pool water (680.26(C)): if no bonded part touches the water, add a corrosion-resistant conductive surface with at least 9 sq in. in contact with it.
Worked example: one backyard pool, six calls
| Item | 2017 NEC call |
|---|---|
| Pump, 240 V, 20 A, single-phase | GFCI required (680.21(C)). The pump area is a corrosive environment (680.14(A)), so use RMC, IMC, rigid PVC, RTRC or MC listed for the location, with an insulated copper EGC of 12 AWG or larger. |
| Deck receptacle 4 ft from the wall | Not allowed. Move it to 6 ft or more. |
| Patio light 3 ft out, 10 ft high | Not allowed for new outdoor work. Within 5 ft it needs 12 ft. |
| Patio light 8 ft out, 6 ft above the water, rigidly attached | Allowed without GFCI (680.22(B)(4)). |
| Switch 4 ft out, no barrier, not listed for the location | Not allowed. 5 ft minimum. |
| Deck with no usable reinforcing steel | 8 AWG bare solid copper ring, 18 in. to 24 in. from the wall, 4 in. to 6 in. below subgrade, tied in at four or more evenly spaced points. |
Article 680 traps on a 2017 exam
- Getting the pump GFCI scope wrong. 2017 covers single-phase 120 V through 240 V pump outlets of any ampere rating, but no 3-phase pumps.
- Stranded or 10 AWG bonding. Wrong. Solid copper, 8 AWG minimum.
- 12 ft vs 7 ft 6 in. The lower height is indoors only, with GFCI and the right equipment.
- Confusing 18 in. and 3 ft. The copper ring sits 18 in. to 24 in. out. The bonded perimeter surface runs 3 ft out.
- Overhead conductor clearances. Article 680 has its own clearance table. Look it up in your 2017 book, not a summary written for another edition.
2017 pool wiring quiz: 5 questions
Answer from your 2017 NEC, then open the key.
Question 1
Where must the required general-purpose receptacle at a permanently installed pool be, measured from the inside wall (680.22(A)(1))?
- 5 ft to 10 ft
- 6 ft to 20 ft
- 10 ft to 20 ft
- 6 ft to 15 ft
Question 2
An outdoor luminaire is 3 ft horizontally from the inside wall. What is its minimum height above the maximum water level?
- 7 ft 6 in.
- 10 ft
- 12 ft
- 15 ft
Question 3
Without usable reinforcing steel, what conductor does 680.26(B)(2) require for perimeter bonding?
- 10 AWG bare solid copper
- 8 AWG bare solid copper
- 6 AWG stranded copper
- 4 AWG bare aluminum
Question 4
Under the 2017 NEC, which pool pump outlet must have GFCI protection under 680.21(C)?
- 208 V, 20 A, 3-phase
- 240 V, 30 A, single-phase
- 480 V, 15 A, 3-phase
- 208 V, 30 A, 3-phase
Question 5
An indoor pool has a totally enclosed luminaire on a GFCI-protected circuit. What is its minimum height above the maximum water level?
- 5 ft
- 7 ft 6 in.
- 10 ft
- 12 ft
Answer key
Show the answer to question 1Hide the answer to question 1
1. B, 6 ft to 20 ft (680.22(A)(1))
And no more than 6 ft 6 in. above the floor, platform or grade serving the pool.
Show the answer to question 2Hide the answer to question 2
2. C, 12 ft (680.22(B)(1))
7 ft 6 in. is the indoor GFCI reduction.
Show the answer to question 3Hide the answer to question 3
3. B, 8 AWG bare solid copper (680.26(B)(2)(b))
Placed 18 in. to 24 in. from the inside walls and 4 in. to 6 in. below the subgrade.
Show the answer to question 4Hide the answer to question 4
4. B, 240 V, 30 A, single-phase (680.21(C))
The 2017 rule covers pool pump outlets on single-phase 120 V through 240 V branch circuits, with no ampere limit. A, C and D are 3-phase. The broader 2020 rule would also reach A and D, which are 120 V to ground and 60 A or less.
Show the answer to question 5Hide the answer to question 5
5. B, 7 ft 6 in. (680.22(B)(2))
Without GFCI, the 12 ft clearance applies.
Pool wiring FAQ (2017 NEC)
How far must a receptacle be from a pool under the 2017 NEC?
At least 6 ft from the inside wall. At a permanently installed pool, at least one 125 V, 15 A or 20 A general-purpose receptacle must sit between 6 ft and 20 ft away. All 125 V, 15 A and 20 A receptacles within 20 ft need GFCI protection.
What are the pool bonding requirements in the 2017 NEC?
Bond the listed parts with solid copper of at least 8 AWG (680.26(B)). Include the perimeter surface 3 ft out from the inside walls. Tie it to the pool steel or copper grid at four or more evenly spaced points.
Does a pool pump need GFCI under the 2017 NEC?
Yes, when the outlet is on a single-phase, 120 V through 240 V branch circuit of any ampere rating, whether plugged in or hard-wired (680.21(C)). 3-phase pumps fall outside the 2017 rule. The 2020 NEC widened it to pool motors up to 150 V to ground and 60 A, single- or 3-phase.
How high must a light be over a pool?
Outdoors, at least 12 ft above the maximum water level when over the pool or within 5 ft horizontally of the inside wall. Indoors, a totally enclosed luminaire on a GFCI-protected circuit may be 7 ft 6 in.
Turn Article 680 into easy points
Pool items reward fast lookups. Practice them against the clock.
Studying for Tennessee, Nevada, Arizona, Kansas or Missouri? The 2017 NEC exam prep course ($495) covers all five, and Tennessee candidates can pick the Tennessee self-study package.
Sources
- NFPA 70, 2017 edition: 680.14, 680.21(A) and (C), 680.22(A) through (C), 680.26(B) and (C), 250.122
- NFPA 70, 2020 edition: 680.21(C), for the comparison only
Reviewed November 6, 2026. NEC references are to the 2017 edition.