Under NFPA 70E, a qualified person is someone who has demonstrated the skills and knowledge to work on specific electrical equipment and has had safety training to identify its hazards and reduce the risk. A license or a class certificate doesn't make someone qualified on its own. The employer trains each person, keeps the record and checks at least once a year that they work safely. One person can be qualified for one task and unqualified for another.
| At a glance | Qualified person |
|---|---|
| Definition | Demonstrated skills and knowledge of the equipment, plus safety training on its hazards (NFPA 70E, Article 100) |
| Training rule | NFPA 70E 110.4(A)(2), 2027 edition |
| Scope | Specific equipment and tasks. Qualified for some, unqualified for others. |
| Who decides | The employer |
| Checked | By regular supervision, or inspections at least once a year |
| Retraining | At least every 3 years |
| OSHA version | 29 CFR 1910.399 (definition) and 1910.332(b)(3) (training) |
Training a crew toward qualified status? JCR teaches private NFPA 70E classes at your site or live on Zoom. Send us the headcount, the work your people do and your deadline.
Or call (704) 696-8555.
What is a qualified person under NFPA 70E?
NFPA 70E defines a qualified person in Article 100. The definition has two parts, and both must be true.
- Skills and knowledge. The person has demonstrated that they understand how the electrical equipment and installations are built and how they operate.
- Safety training. The person has been trained to identify the hazards and reduce the risk.
The word "demonstrated" matters. Sitting through a class isn't enough. The person has to show the skill.
OSHA's definition in 29 CFR 1910.399 is nearly the same. It calls for training plus demonstrated skills and knowledge of electric equipment, installations and the hazards involved.
An unqualified person is anyone who is not a qualified person.
What training does a qualified person need?
NFPA 70E 110.4(A)(2) sets the list. Every qualified person must be trained in:
- How the equipment is built and operates, or the specific work method
- Identifying and avoiding the electrical hazards of that equipment or method
- The proper use of precautionary techniques, electrical policies and procedures, PPE, insulating and shielding materials, and insulated tools and test equipment
The limited approach boundary is the shock-protection distance around exposed energized parts. To work inside it, a qualified person needs four more things (110.4(A)(2)(c)):
- Telling exposed energized parts from the other parts of the equipment
- Determining the nominal voltage of exposed energized parts
- The approach distances in Table 130.4(E)(a) and Table 130.4(E)(b) for the voltages they will face
- The decision-making to plan the job, identify the hazards, assess the risk and select risk controls, including PPE
Test instruments have their own rule. Anyone who uses one must be trained to select an instrument rated for the job, use it correctly and know its limits (110.4(A)(2)(e)). They must also demonstrate how to test for the absence of voltage and read what the instrument shows (110.4(A)(2)(f)).
Is a licensed electrician automatically a qualified person?
No, a license alone doesn't make an electrician a qualified person. A state license shows trade competence. NFPA 70E qualification is tied to specific equipment and tasks at your workplace.
The 2027 edition says it directly, and it is one of the changes in NFPA 70E 2027. A person can be considered qualified for certain equipment and tasks and unqualified for others (110.4(A)(2)(b)). OSHA's note to its own definition says the same thing and calls that outcome likely.
Example: an electrician who troubleshoots 480-volt motor controls every day may be qualified for that work. The same electrician is unqualified to rack medium-voltage breakers until they are trained and have shown they can do it safely.
Can an apprentice or trainee be a qualified person?
An apprentice or trainee can be a qualified person for specific duties. NFPA 70E 110.4(A)(2)(d) treats an employee in on-the-job training as qualified for a duty when both of these are true:
- They have shown they can do that specific duty safely at their level of training.
- They are under the direct supervision of a qualified person.
OSHA's definition carries the same allowance in its second note.
Who decides that someone is qualified?
The employer decides who is qualified. NFPA doesn't qualify workers, and neither does a state board or a training company. Under NFPA 70E and OSHA, three jobs fall to the employer.
- Train. Give each person the training in 110.4(A) for their equipment and tasks. It can be classroom, on-the-job or both (110.4(A)(5)).
- Document. Record each employee's name, the training content and the dates. Make the record when the employee demonstrates proficiency, and keep it for as long as they work for you (110.4(A)(6)).
- Verify. Confirm through regular supervision, or inspections at least once a year, that each employee follows the safe work practices 70E requires (110.4(A)(2)(g)).
A certificate from a 70E class supports the record. It doesn't replace the employer's call on who can do which task. Our NFPA 70E certification guide explains what a certificate does and doesn't prove.
What training do unqualified persons need?
Unqualified persons must be trained in, and be familiar with, the electrical safety practices necessary for their own safety (110.4(A)(3)).
These are people who work near electrical equipment but don't work on it. OSHA's list of higher-risk jobs includes machine operators, painters and welders (1910.332, Table S-4).
How long does qualified person status last?
Qualified status isn't a card with an expiration date. It holds only while the training is current and the person keeps working safely. NFPA 70E sets these deadlines:
- Every 3 years at most: retraining in safe work practices and in changes to the standard (110.4(A)(4)).
- Every year: the employer's supervision or inspection check (110.4(A)(2)(g)).
- Every year: refresher training in safely releasing a shock victim, for employees exposed to shock hazards and those responsible for the release (110.4(C)(1)).
- Sooner: when job duties change, when new equipment or procedures arrive, or when a check shows someone isn't following safe practices.
Our guide to how long NFPA 70E training is good for covers each retraining trigger.
How JCR helps you qualify a crew
- Tell us who is attending. Electricians, maintenance techs, operators, supervisors or a mix, and the equipment they work on.
- We teach the 70E safety training. Victor Ring, an NFPA Certified Electrical Safety Compliance Professional (CESCP), covers shock and arc flash hazards, risk assessment, boundaries, lockout/tagout, PPE and test instruments.
- You finish the job on site. You confirm each person's skills on your equipment and keep the training record. We send completion records for your files.
JCR teaches at sites in North Carolina, Virginia, South Carolina, Georgia and Tennessee, or live on Zoom. Private seminars start at $3,500 per day. Request a quote or call (704) 696-8555.
More questions about qualified persons
Does a 70E class make my employees qualified persons?
Not by itself. A class delivers the safety training. The employer still has to confirm each person's skills on the actual equipment, document it and verify safe work each year.
Is OSHA's definition the same as NFPA 70E's?
Nearly. Both require training plus demonstrated skills and knowledge. OSHA's definition is in 29 CFR 1910.399, and its added training list for qualified persons is in 1910.332(b)(3).
Does NFPA certify qualified persons?
No. NFPA writes the standard. It doesn't qualify or certify the workers on your crew. NFPA 70E leaves that to the employer.
Can someone be qualified at one employer and not at the next?
Yes. Qualification depends on the equipment, the tasks and the employer's procedures. A new employer has to make its own call and keep its own training record.
Related JCR guides
Official sources
JCR checked NFPA 70E (2027) in NFPA LiNK and the OSHA pages above on November 18, 2026.