NFPA 70B is the standard for maintaining electrical equipment, and it requires everyone who does that maintenance to be trained for the tasks they perform. The training has to cover the specific tasks, test methods, test equipment, PPE and equipment hazards. 70B sets no certification and no fixed renewal date. Retraining is due when equipment, procedures or duties change. JCR teaches 70B classes at your site or live on Zoom, alone or paired with 70E.
| At a glance | NFPA 70B, 2026 edition |
|---|---|
| What it is | Standard for Electrical Equipment Maintenance |
| Who must be trained | Everyone assigned maintenance work under the program |
| Training covers | Tasks, test methods, test equipment, PPE and equipment hazards |
| Retraining | When equipment, procedures, duties or the standard change. No fixed interval. |
| Certification | None required. The employer documents the training. |
| JCR class | At your site in NC, SC, VA, GA or TN, or live on Zoom. Request a quote. |
Need 70B training for your maintenance team? Tell us the headcount, site, equipment and timing. We can teach 70B alone or with 70E in the same visit.
Or call (704) 696-8555.
What is NFPA 70B?
NFPA 70B is the Standard for Electrical Equipment Maintenance. It covers corrective, preventive and predictive maintenance of electrical, electronic and communications equipment (1.1).
It applies to the kind of equipment found in industrial plants, institutional and commercial buildings, and large multifamily complexes (1.3.1). For decades it was a recommended practice. The 2023 edition made it a standard, and its wording changed from should to shall. The current edition is 2026.
Is NFPA 70B mandatory?
NFPA 70B is written as a mandatory standard, but no OSHA regulation adopts it by name. It applies to your site when someone with authority over it requires it, such as your company, an insurer, a contract or a local authority.
It also ties into NFPA 70E, the electrical safety standard that OSHA says employers can use as a guide. 70E requires your electrical safety program to consider the condition of maintenance of your equipment (Article 110). A 70B program is how you establish that condition.
Who needs NFPA 70B training?
Everyone assigned maintenance work under your electrical maintenance program needs training. 70B requires maintenance to be done by qualified persons (5.1.1), and people assigned to the program must be qualified for their tasks (4.3.2).
In practice that means:
- Maintenance electricians and technicians
- Facility and plant maintenance teams
- Contractors who service a customer's equipment
- The program coordinator and the supervisors who plan the work
Someone still in on-the-job training can do specific tasks under the direct supervision of a qualified person, once they've shown they can do those tasks safely (4.3.3.1).
What does 70B training have to cover?
Training must match the equipment and tasks the person actually handles. Under 4.3.3, a person responsible for maintenance must be trained in:
- The specific maintenance tasks
- Test methods
- Test equipment
- PPE use, where it applies
- The hazards of the equipment or systems being serviced
Cleaning counts too. People assigned to clean equipment need training in the cleaning procedures, the damage cleaning can do, the injury risks and which equipment not to clean (4.8.1.2).
The employer has two follow-up duties:
- Check the work. Confirm through regular supervision, or inspections at least once a year, that each person follows the maintenance and testing procedures (4.3.3.2).
- Keep records. Document the training content, the person's name and the dates. Make the record when the person demonstrates proficiency and keep it for their whole employment (4.3.3.4).
How often is NFPA 70B retraining required?
NFPA 70B sets no fixed retraining interval. Training or retraining is required when any of these happens (4.3.3.3):
- Supervision or the yearly inspection shows the person isn't following procedures.
- New technology, new equipment or changed procedures call for different methods.
- The person needs to review tasks done less than once a year.
- The person's duties change to include new work.
- A new edition of 70B, or a new version of your maintenance program, changes what the person does.
NFPA 70E works differently. It caps the gap between trainings at 3 years. Crews that need both can take them together.
What an electrical maintenance program has to include
The electrical maintenance program (EMP) is the equipment owner's documented plan for inspecting, testing and servicing equipment (4.2.1). The 2026 edition lists 11 required elements (4.2.4.2):
- How the condition of maintenance affects electrical safety
- An electrical safety program that addresses the condition of maintenance
- Who is responsible for each part of the program
- A survey of the equipment to set maintenance needs and priorities
- Written maintenance procedures
- An inspection, servicing and testing plan
- Records for maintenance, equipment and personnel, and how long they're kept
- A process for deciding on and documenting corrective work
- A process for designing new installations so they're easier to maintain
- A review process that uses failures and findings to improve the program
- A cybersecurity risk assessment for networked control systems
The owner names an EMP coordinator (4.3.1), who sets the scope of work and builds a prioritized maintenance plan (4.4.1). The program must be audited at least every 5 years (4.2.7).
How 70B sets maintenance intervals
Chapter 9 bases each interval on an equipment condition assessment. Equipment is rated in three areas, and the highest (worst) rating controls (9.2):
- Physical condition: Condition 1 is like new, with a clean, dry, tight enclosure, no open findings, and past maintenance done per the EMP.
- Criticality: how important the equipment is, rated Condition 1, 2 or 3.
- Operating environment: harsh chemicals, contaminants or extreme operating conditions put equipment in Condition 3.
Table 9.3.2 then sets intervals by equipment type and condition. For example, infrared thermography of all equipment is every 12 months in Condition 1 or 2, and every 6 months in Condition 3. Once you set a schedule, you follow it for at least two intervals before changing it, unless something fails unexpectedly (9.1.2.1).
NFPA 70B vs. NFPA 70E
NFPA 70E covers how people work safely on or near electrical equipment. NFPA 70B covers how the equipment itself is kept in safe, reliable condition. Each points to the other:
- 70B says safety-related work practices during maintenance follow NFPA 70E or the applicable codes (5.1.2).
- 70B says the EMP must work together with the electrical safety program (4.2.4.1).
- The 2027 edition of 70E says the electrical safety program must consider the condition of maintenance of equipment (Article 110).
70E keeps the worker safe during the task. 70B makes sure the equipment is in the condition the 70E risk assessment assumes. That is why maintenance crews often need both.
70B training from JCR
JCR teaches private 70B classes for maintenance electricians, facility teams, EMP coordinators and supervisors. We teach at your site in North Carolina, South Carolina, Virginia, Georgia or Tennessee, or live on Zoom for teams at several locations.
Tell us what equipment your people maintain and whether you already have an EMP. We build the agenda around that, and we can add 70E to the same visit.
Private seminars start at $3,500 per day, taught by Victor Ring, an NFPA Certified Electrical Safety Compliance Professional (CESCP). Request a quote or call (704) 696-8555.
More questions about NFPA 70B
Is there an NFPA 70B certification?
70B doesn't require one. It requires the employer to document each person's training, including the content, the person's name and the dates.
Can JCR teach 70B and 70E in one visit?
Yes. We can teach them back to back, or build one combined agenda for crews that both maintain equipment and work near energized parts.
Related JCR guides
Official sources
JCR checked NFPA 70B (2026) and NFPA 70E (2027) in NFPA LiNK on November 18, 2026.