Motor Overload Sizing Guide: 430.32 at 115%, 125% and 140% (2026)

Sizing motor overload protection under 2017 NEC 430.32 - JCR Productions

Motor overload sizing under NEC 430.32 comes down to 115%, 125% and 140% of the nameplate full-load current, never the table current. Under 2017 NEC 430.32(A)(1), the overload may trip at no more than 125% of nameplate current when the motor is marked with a service factor of 1.15 or more or a temperature rise of 40°C or less, and 115% for every other motor. If that setting won't start the motor, 430.32(C) lets you go up to 140% or 130%. The percentages are the same in the 2017 and 2020 editions. If you only need the service-factor question exams miss most, JCR's shorter motor overload and service factor explainer covers it; this page is the full sizing guide.

Test your speed on the free 25-question 2017 NEC mock exam. It has a 430.32(C) question, gives instant feedback and shows the NEC reference for every answer.

Testing in Tennessee, Nevada, Arizona or Kansas? Those exams grade on the 2017 NEC, and motor questions show up on all of them. JCR's 2017 NEC package drills breakers, conductors and overloads until you stop mixing them up.

$495 gets you 100 video lessons (21 hours), a 152-page printed 2017 NEC manual, permanent code tabs, a printed mock booklet and 312 online questions with a full 100-question timed mock.

Get the 2017 NEC package: $495

Want a warm-up? Run the free 25-question mock before you buy.

Motor overload sizing chart: 430.32 at 115%, 125%, 130% and 140%

430.32(A)(1) covers a separate overload device on a continuous-duty motor rated more than 1 hp. Find the nameplate marking in the left column, then read across.

Motor nameplate marking Maximum trip, 430.32(A)(1) If it won't start, 430.32(C)
Service factor 1.15 or more 125% of nameplate FLA Up to 140%
Temperature rise 40°C or less 125% of nameplate FLA Up to 140%
All other motors 115% of nameplate FLA Up to 130%

Only one of the two 125% conditions has to be true. A motor marked SF 1.0 with a 40°C rise still gets 125%. The branch-circuit breaker is a separate calculation from Table 430.52; JCR's motor breaker sizing guide walks through it.

The trap: nameplate current, not table current

Article 430 uses two different currents, and the exam tests whether you know which one goes where:

  • Overloads use the nameplate. 430.6(A)(2) says separate motor overload protection is based on the motor nameplate current rating.
  • Conductors and breakers use the table. 430.6(A)(1) sends you to Table 430.248 (single-phase) or Table 430.250 (three-phase) for conductor ampacity and branch-circuit short-circuit and ground-fault protection.
What you're sizing Current to use Rule
Overload protection Nameplate FLA 430.6(A)(2), 430.32: 115% or 125%, no rounding up
Branch-circuit conductors Table FLC 430.6(A)(1), 430.22: 125%
Branch-circuit breaker or fuse Table FLC 430.6(A)(1), Table 430.52: 250% for an inverse time breaker on most motors, next standard size up allowed

Notice that 125% shows up twice. Conductors are 125% of the table FLC. A 1.15 SF overload is 125% of the nameplate FLA. Same percentage, different starting number, different answer.

Motor overload calculation: three worked examples

Example 1: 10 hp, 230 V, three-phase, SF 1.15

Nameplate FLA is 26 A. Table 430.250 lists 28 A for this motor.

  • Overload: 26 A × 125% = 32.5 A maximum. If it won't start: 26 A × 140% = 36.4 A.
  • Conductors: 28 A × 125% = 35 A minimum ampacity.
  • Inverse time breaker: 28 A × 250% = 70 A, a standard size.

Use 28 A for the overload and you get 35 A, the most common wrong answer.

Example 2: 5 hp, 460 V, three-phase, SF 1.0, 50°C rise

Nameplate FLA is 7.0 A. The service factor is under 1.15 and the rise is over 40°C, so it falls under all other motors. Table 430.250 lists 7.6 A.

  • Overload: 7.0 A × 115% = 8.05 A maximum. If it won't start: 7.0 A × 130% = 9.1 A.
  • Conductors: 7.6 A × 125% = 9.5 A minimum ampacity.
  • Inverse time breaker: 7.6 A × 250% = 19 A, so the next standard size, 20 A.

Example 3: 3 hp, 230 V, single-phase, 40°C rise

Nameplate FLA is 16 A, SF 1.0. The 40°C rise earns the 125% column. Table 430.248 lists 17 A.

  • Overload: 16 A × 125% = 20 A maximum. If it won't start: 16 A × 140% = 22.4 A.
  • Conductors: 17 A × 125% = 21.25 A minimum ampacity.
  • Inverse time breaker: 17 A × 250% = 42.5 A, so the next standard size, 45 A.

Exam traps on 430.32

  • Table current for the overload. If the question gives both a nameplate FLA and a horsepower, the overload answer comes from the nameplate.
  • Jumping straight to 140%. 430.32(C) is only for a motor that won't start or carry its load at the (A)(1) setting. A plain maximum-overload question means 115% or 125%.
  • Rounding up. The next-standard-size rule belongs to the breaker in 430.52(C)(1) Exception No. 1. 430.32 has no round-up. 32.5 A means 32.5 A.
  • Missing the 40°C rise. An SF 1.0 motor still gets 125% if it's marked 40°C rise or less.
  • Using 2020 table numbers. 430.32 didn't change, but the conductor tables did. In the 2017 NEC you size the motor conductors from Table 310.15(B)(16), which the 2020 edition renumbered Table 310.16. Tennessee, Nevada, Arizona and Kansas score the 2017 number.

430.32 practice quiz: 5 questions

Work these with your 2017 NEC open, write down your answers, then open the explanations.

Question 1

A continuous-duty motor has a nameplate FLA of 40 A and a service factor of 1.15. What is the maximum rating of a separate overload device under 430.32(A)(1)?

  1. 46 A
  2. 50 A
  3. 52 A
  4. 56 A

Question 2

A motor is marked with a service factor of 1.0 and a temperature rise of 50°C. Its nameplate FLA is 20 A. What is the maximum overload rating?

  1. 23 A
  2. 25 A
  3. 26 A
  4. 28 A

Question 3

The motor in Question 1 won't start with an overload sized at 125%. What is the most 430.32(C) allows?

  1. 50 A
  2. 52 A
  3. 56 A
  4. 60 A

Question 4

Which current does the 2017 NEC require you to use when sizing separate motor overload protection?

  1. Full-load current from Table 430.250
  2. Motor nameplate current rating
  3. Locked-rotor current
  4. 125% of the table full-load current

Question 5

A 25 hp, 460 V, three-phase motor has a nameplate FLA of 32 A and a service factor of 1.15. Table 430.250 lists 34 A. What is the maximum overload rating?

  1. 36.8 A
  2. 40 A
  3. 42.5 A
  4. 44.8 A

Answer key with 2017 NEC sections

Show the answer to question 1Hide the answer to question 1

1. B, 50 A (430.32(A)(1))

SF 1.15 or more gets 125%: 40 A × 1.25 = 50 A. 46 A is the 115% answer, and 56 A is the 430.32(C) limit, which needs a starting problem first.

Show the answer to question 2Hide the answer to question 2

2. A, 23 A (430.32(A)(1))

The SF is under 1.15 and the rise is over 40°C, so neither 125% condition applies. All other motors get 115%: 20 A × 1.15 = 23 A.

Show the answer to question 3Hide the answer to question 3

3. C, 56 A (430.32(C))

For an SF 1.15 motor, 430.32(C) allows up to 140%: 40 A × 1.40 = 56 A. There is no rounding up to 60 A.

Show the answer to question 4Hide the answer to question 4

4. B, the nameplate current (430.6(A)(2))

430.6(A)(2) bases separate overload protection on the motor nameplate current. The table values in 430.6(A)(1) are for conductors and branch-circuit short-circuit and ground-fault protection.

Show the answer to question 5Hide the answer to question 5

5. B, 40 A (430.6(A)(2) and 430.32(A)(1))

Use the nameplate 32 A, not the table 34 A: 32 A × 1.25 = 40 A. 42.5 A is the table-current trap, 36.8 A uses 115% and 44.8 A is the 140% starting limit.

Motor overload sizing FAQ

Do you size motor overloads from the nameplate or the NEC table?

The nameplate. 430.6(A)(2) requires the motor nameplate current for separate overload protection. Conductors and the branch-circuit breaker use the Table 430.248 or 430.250 value.

What is the maximum overload for a motor with a 1.15 service factor?

125% of the nameplate full-load current under 430.32(A)(1). If that setting won't start the motor or carry the load, 430.32(C) allows up to 140%.

Do you round motor overloads up to the next standard size?

No. The next-size-up rule is for the branch-circuit breaker or fuse in 430.52. The 430.32 percentages are maximums.

Did 430.32 change between the 2017 and 2020 NEC?

No. The 115%, 125%, 130% and 140% values are the same in both editions. The tables around it, like the conductor ampacity table, were renumbered in 2020.

How do I calculate motor overload size?

Multiply the nameplate full-load amps by 125% if the motor is marked SF 1.15 or more or 40°C rise or less, or by 115% for any other motor. Pick an overload device or setting that trips at or below that number. Go to 140% or 130% only if the motor won't start or carry its load.

Practice motor questions on the 2017 NEC

Start with free questions, then drill motors, ampacity and load calculations on the edition your exam grades.

Take the free 2017 NEC mock

See the 2017 NEC self-study package: $495. Testing in Tennessee? Use the Tennessee package.

Sources

Reviewed November 6, 2026. NEC references are to the 2017 edition.

  • Victor's class is always very informative and enjoyable to attend every year I go.

    Chase Hall
    2 weeks ago
  • Awesome Class Victor is a great instructor

    Tom P
    3 weeks ago
  • Great class. Definitely gave me the confidence to take the exam o,I didn't have before.

    Erin Lacoille
    3 weeks ago
  • It's the perfect method to ace the exam 👍

    Oly Castro
    3 weeks ago
  • Did the CEU 8-hour course with Victor. It was great. He broke down how professionals should address and use the NFPA. Thoroughly enjoyed the knowledge and experiences.

    Seth McCurty
    5 months ago
  • I have been attending JCR Productions now for 30+ years. Victor Ring and Jeff Rodriguez have instructed me from my apprenticeship days to passing my unlimited license exam. They have been a huge part of helping me to gain the knowledge I need to be successful in the electrical field. They make it fun as well. I have recommend JCR Productions for exam prep and CE courses to hundreds of people over the last 30+ years. I would not go anywhere else!

    Sean Ryan
    3 months ago
  • Victor Ring was my instructor and he did an amazing job at being very informative as well as interactive, and his concern for practicing safety was priority #1. Definitely looking forward to learning much more from this group.

    Travis Hall
    4 months ago
  • I have taken the CE classes with JCR for the last 13 years. I hold 15 state master's and 6 contractor's license and I look forward to going every year. Victor Ring is a well-educated and an excellent instructor. I would recommend this program for your CE requirements or your master's exam prep.

    terry blair
    3 months ago
  • I have enjoyed going to Victor's CEU classes since I first started attending them a few years ago. He has a lot of experience and is very knowledgeable on the NEC and in the electrical industry. I plan to do all my CEU's with JCR every year.

    Josh Boling
    6 months ago
  • I have attended JCR classes on several occasions. I used their exam prep and feel very confident in saying it was a large portion of my success. I continue to use JCR classes with Victor Ring for CE credits and have no intention of stopping in the future.

    Michael Griffin
    5 months ago
  • I completed my 8-hour Continuing Education Electrical Code course with JCR Productions and had a great experience. If you need to complete your required hours to maintain your electrical license, this course is an excellent choice. Victor Ring kept the class upbeat, engaging, and easy to follow. He does a great job breaking down the material and showing simpler, more efficient ways to navigate the NEC Code book, which makes the information practical and immediately useful in the field. Highly recommend this course to any electrician looking for a professional, informative, and enjoyable way to get their continuing education hours completed.

    Matt Pressley
    5 months ago
  • The exam prep class was great. Victor is very knowledgeable and takes making sure everyone is ready to take the test personally. Never met anyone that cares about people and how their future. I will defiantly going to taking more classes in the future.

    michael taylor
    6 months ago
  • Always learn something new from every class I have taken from JCR production. Really enjoy the way Mr Ring teaches class. Thank you ! Ken Koehler

    Ken Koehler
    3 months ago
  • Taken multiple JCR classes, specifically with Mr. Victor ring, love his classes. He’s extremely knowledgeable in his field and can present info in a way that’s easy to learn. Will continue using him for all future classes and continuing education credits.

    Brandon Whitley
    9 months ago
  • Victor Ring has a gifted mind for understanding electricity and he shares that information in an impressively articulate manner. He is a great teacher, and I would recommend JCR to any professional electrician who needs to brush up on their skills and learn new methods of installation to serve our customers and ourselves well. Big ups to Vic! -Willis Tisdale Greenville SC

  • I always thoroughly enjoy the seminars with Victor Ring and JCR . Victors knowledge of the material he is teaching and his delivery is superb. Which is matched with his office staff who are very helpful.

    Robert Carignan
    7 months ago
  • Highly Recommend the Exam Preparation class!! Victor is great! I will continue using JCR in the future.

    Corey Hutchens
    6 months ago
  • I recently attended the Exam Prep Class and I was extremely impressed with Mr. Victor's approach to navigating the code book. He took what can be an intimidating book and simplified it in a way anyone could understand. He is without a doubt, the Best teacher I have had the privilege of learning from. I will be using him for my continuing education classes in the future.

    Mitch Grizzard
    5 months ago
  • This was absolutely the best class I have ever attended during my journey in the trade! Victor is awesome and extremely knowledgeable! He truly inspires you through his teaching to become the best you can be! Awesome!

    Ronald whitener
    6 months ago
  • I recently decided to go for my electrical license. Taking the JCR test prep really helped me to better understand navigating the code along with some additional methods for using the code that helped clarify the book. I will continue using JCR for my continuing ed along with other resources. Highly recommend taking this exam prep!

    Micah Barfield
    8 months ago
  • As usual Victor's class was highly enjoyable and energetic. He is a 1st rate instructor, and JCR is the only place I'll go for exam and CE studies.

    Brian Chase
    6 months ago
  • Victor was fantastic . The class was very informative. The study guide from Jeff and Victor were a driving force behind me passing my electrical licensing exam . I can’t thank them enough. They changed my and my family’s life for the better . I wish I could give more than 5 stars . Will only be doing CE with the JCR team .

    Michael Lewis
    6 months ago
  • I have been using JCR Productions for more than a decade and am never disappointed. Victor is bringing some fresh trainings that apply directly to someone that owns their own electrical business.

    Jason Fradenburgh
    6 months ago
  • I have been going to JCR for my North Carolina license continuing education since 2001 and this class has always kept me on top of the code changes and a refresher of all the material in the code book. I have gone to other continuing education classes for licenses in other states and JCR has always been my favorite.

    Tom Francisco
    6 months ago