Motor overload sizing under NEC 430.32 comes down to 115%, 125% and 140% of the nameplate full-load current, never the table current. Under 2017 NEC 430.32(A)(1), the overload may trip at no more than 125% of nameplate current when the motor is marked with a service factor of 1.15 or more or a temperature rise of 40°C or less, and 115% for every other motor. If that setting won't start the motor, 430.32(C) lets you go up to 140% or 130%. The percentages are the same in the 2017 and 2020 editions. If you only need the service-factor question exams miss most, JCR's shorter motor overload and service factor explainer covers it; this page is the full sizing guide.
Test your speed on the free 25-question 2017 NEC mock exam. It has a 430.32(C) question, gives instant feedback and shows the NEC reference for every answer.
Testing in Tennessee, Nevada, Arizona or Kansas? Those exams grade on the 2017 NEC, and motor questions show up on all of them. JCR's 2017 NEC package drills breakers, conductors and overloads until you stop mixing them up.
$495 gets you 100 video lessons (21 hours), a 152-page printed 2017 NEC manual, permanent code tabs, a printed mock booklet and 312 online questions with a full 100-question timed mock.
Get the 2017 NEC package: $495
Want a warm-up? Run the free 25-question mock before you buy.
Motor overload sizing chart: 430.32 at 115%, 125%, 130% and 140%
430.32(A)(1) covers a separate overload device on a continuous-duty motor rated more than 1 hp. Find the nameplate marking in the left column, then read across.
| Motor nameplate marking | Maximum trip, 430.32(A)(1) | If it won't start, 430.32(C) |
|---|---|---|
| Service factor 1.15 or more | 125% of nameplate FLA | Up to 140% |
| Temperature rise 40°C or less | 125% of nameplate FLA | Up to 140% |
| All other motors | 115% of nameplate FLA | Up to 130% |
Only one of the two 125% conditions has to be true. A motor marked SF 1.0 with a 40°C rise still gets 125%. The branch-circuit breaker is a separate calculation from Table 430.52; JCR's motor breaker sizing guide walks through it.
The trap: nameplate current, not table current
Article 430 uses two different currents, and the exam tests whether you know which one goes where:
- Overloads use the nameplate. 430.6(A)(2) says separate motor overload protection is based on the motor nameplate current rating.
- Conductors and breakers use the table. 430.6(A)(1) sends you to Table 430.248 (single-phase) or Table 430.250 (three-phase) for conductor ampacity and branch-circuit short-circuit and ground-fault protection.
| What you're sizing | Current to use | Rule |
|---|---|---|
| Overload protection | Nameplate FLA | 430.6(A)(2), 430.32: 115% or 125%, no rounding up |
| Branch-circuit conductors | Table FLC | 430.6(A)(1), 430.22: 125% |
| Branch-circuit breaker or fuse | Table FLC | 430.6(A)(1), Table 430.52: 250% for an inverse time breaker on most motors, next standard size up allowed |
Notice that 125% shows up twice. Conductors are 125% of the table FLC. A 1.15 SF overload is 125% of the nameplate FLA. Same percentage, different starting number, different answer.
Motor overload calculation: three worked examples
Example 1: 10 hp, 230 V, three-phase, SF 1.15
Nameplate FLA is 26 A. Table 430.250 lists 28 A for this motor.
- Overload: 26 A × 125% = 32.5 A maximum. If it won't start: 26 A × 140% = 36.4 A.
- Conductors: 28 A × 125% = 35 A minimum ampacity.
- Inverse time breaker: 28 A × 250% = 70 A, a standard size.
Use 28 A for the overload and you get 35 A, the most common wrong answer.
Example 2: 5 hp, 460 V, three-phase, SF 1.0, 50°C rise
Nameplate FLA is 7.0 A. The service factor is under 1.15 and the rise is over 40°C, so it falls under all other motors. Table 430.250 lists 7.6 A.
- Overload: 7.0 A × 115% = 8.05 A maximum. If it won't start: 7.0 A × 130% = 9.1 A.
- Conductors: 7.6 A × 125% = 9.5 A minimum ampacity.
- Inverse time breaker: 7.6 A × 250% = 19 A, so the next standard size, 20 A.
Example 3: 3 hp, 230 V, single-phase, 40°C rise
Nameplate FLA is 16 A, SF 1.0. The 40°C rise earns the 125% column. Table 430.248 lists 17 A.
- Overload: 16 A × 125% = 20 A maximum. If it won't start: 16 A × 140% = 22.4 A.
- Conductors: 17 A × 125% = 21.25 A minimum ampacity.
- Inverse time breaker: 17 A × 250% = 42.5 A, so the next standard size, 45 A.
Exam traps on 430.32
- Table current for the overload. If the question gives both a nameplate FLA and a horsepower, the overload answer comes from the nameplate.
- Jumping straight to 140%. 430.32(C) is only for a motor that won't start or carry its load at the (A)(1) setting. A plain maximum-overload question means 115% or 125%.
- Rounding up. The next-standard-size rule belongs to the breaker in 430.52(C)(1) Exception No. 1. 430.32 has no round-up. 32.5 A means 32.5 A.
- Missing the 40°C rise. An SF 1.0 motor still gets 125% if it's marked 40°C rise or less.
- Using 2020 table numbers. 430.32 didn't change, but the conductor tables did. In the 2017 NEC you size the motor conductors from Table 310.15(B)(16), which the 2020 edition renumbered Table 310.16. Tennessee, Nevada, Arizona and Kansas score the 2017 number.
430.32 practice quiz: 5 questions
Work these with your 2017 NEC open, write down your answers, then open the explanations.
Question 1
A continuous-duty motor has a nameplate FLA of 40 A and a service factor of 1.15. What is the maximum rating of a separate overload device under 430.32(A)(1)?
- 46 A
- 50 A
- 52 A
- 56 A
Question 2
A motor is marked with a service factor of 1.0 and a temperature rise of 50°C. Its nameplate FLA is 20 A. What is the maximum overload rating?
- 23 A
- 25 A
- 26 A
- 28 A
Question 3
The motor in Question 1 won't start with an overload sized at 125%. What is the most 430.32(C) allows?
- 50 A
- 52 A
- 56 A
- 60 A
Question 4
Which current does the 2017 NEC require you to use when sizing separate motor overload protection?
- Full-load current from Table 430.250
- Motor nameplate current rating
- Locked-rotor current
- 125% of the table full-load current
Question 5
A 25 hp, 460 V, three-phase motor has a nameplate FLA of 32 A and a service factor of 1.15. Table 430.250 lists 34 A. What is the maximum overload rating?
- 36.8 A
- 40 A
- 42.5 A
- 44.8 A
Answer key with 2017 NEC sections
Show the answer to question 1Hide the answer to question 1
1. B, 50 A (430.32(A)(1))
SF 1.15 or more gets 125%: 40 A × 1.25 = 50 A. 46 A is the 115% answer, and 56 A is the 430.32(C) limit, which needs a starting problem first.
Show the answer to question 2Hide the answer to question 2
2. A, 23 A (430.32(A)(1))
The SF is under 1.15 and the rise is over 40°C, so neither 125% condition applies. All other motors get 115%: 20 A × 1.15 = 23 A.
Show the answer to question 3Hide the answer to question 3
3. C, 56 A (430.32(C))
For an SF 1.15 motor, 430.32(C) allows up to 140%: 40 A × 1.40 = 56 A. There is no rounding up to 60 A.
Show the answer to question 4Hide the answer to question 4
4. B, the nameplate current (430.6(A)(2))
430.6(A)(2) bases separate overload protection on the motor nameplate current. The table values in 430.6(A)(1) are for conductors and branch-circuit short-circuit and ground-fault protection.
Show the answer to question 5Hide the answer to question 5
5. B, 40 A (430.6(A)(2) and 430.32(A)(1))
Use the nameplate 32 A, not the table 34 A: 32 A × 1.25 = 40 A. 42.5 A is the table-current trap, 36.8 A uses 115% and 44.8 A is the 140% starting limit.
Motor overload sizing FAQ
Do you size motor overloads from the nameplate or the NEC table?
The nameplate. 430.6(A)(2) requires the motor nameplate current for separate overload protection. Conductors and the branch-circuit breaker use the Table 430.248 or 430.250 value.
What is the maximum overload for a motor with a 1.15 service factor?
125% of the nameplate full-load current under 430.32(A)(1). If that setting won't start the motor or carry the load, 430.32(C) allows up to 140%.
Do you round motor overloads up to the next standard size?
No. The next-size-up rule is for the branch-circuit breaker or fuse in 430.52. The 430.32 percentages are maximums.
Did 430.32 change between the 2017 and 2020 NEC?
No. The 115%, 125%, 130% and 140% values are the same in both editions. The tables around it, like the conductor ampacity table, were renumbered in 2020.
How do I calculate motor overload size?
Multiply the nameplate full-load amps by 125% if the motor is marked SF 1.15 or more or 40°C rise or less, or by 115% for any other motor. Pick an overload device or setting that trips at or below that number. Go to 140% or 130% only if the motor won't start or carry its load.
Practice motor questions on the 2017 NEC
Start with free questions, then drill motors, ampacity and load calculations on the edition your exam grades.
See the 2017 NEC self-study package: $495. Testing in Tennessee? Use the Tennessee package.
Sources
- NFPA 70, National Electrical Code, 2017 edition: 430.6(A)(1), 430.6(A)(2), 430.22, 430.32(A)(1), 430.32(C), 430.52(C)(1), Table 430.52, Table 430.248, Table 430.250, Table 310.15(B)(16)
Reviewed November 6, 2026. NEC references are to the 2017 edition.